STR581 is a counter/tachometer/flowmeter. Input may read PNP, NPN signals or Push-pull/line driver types to interface typically with proximity sensors, flow rate sensors, encoders; the input maximum reading frequency is 100KHz.
The device can handle two independent count registers (Counter 1 and Counter 2; Tachometer functionality is provided for Counter 1).
The resolution of the counters is 64bit; display can rescale the font according to the number of digits to be displayed. The measuring unit is customizable.
Four outputs/thresholds are available (2 relay and 2 PNP/digital), free configurable and relatable to the counters/tachometer.
One RS485/Slave serial port with Modbus-RTU protocol allows networking and remote access.
- Dimensions96x48 (Front panel) x 48 mm (1/8Din)
- MaterialBox: polycarbonate V0. Front cover: silicone rubber
- WeightApprox. 165 g
- SealingFront panel: IP54, Box and terminal blocks: IP20
- Operating conditionsTemperature 0..45 °C, humidity 35..95 RH%, max altitude 2000m
- CertificationsCE, UL
ORDERING CODES | STR581-1ABC-T128R |
---|---|
Power supply | 24..230 V AC / DC ±15% 50/60 Hz - galvanic isolation 2,5KV |
Power consumption | 8 Watt/VA |
Display | 2.42" monochrome (yellow) OLED graphic display, 128 x 64 |
Analogue inputs | - |
Digital inputs | 4x PNP/NPN |
Encoder/counter inputs | 1x Encoder/counter 32 bit - NPN, PNP, Push-Pull, Line-driver - max. 100KHz 2 x Counter 64bit - NPN, PNP, Push-Pull - max 100KHz |
Analogue outputs | - |
Digital outputs | 2x PNP 12/24 V DC 25 mA |
Auxiliary Output | 12/24 VDC - 50mA max for sensor supply |
Relais outputs | 2x 2 A - 250 V AC resistive loads |
Serial communication | RS485 (1200..115200 Baud) galvanically isolated |
USB | 1x micro USB for firmware update |
- Functions Digital Counter InputsUp, Down, Lock, Hold, mono/bidirectional encoder readout
- Counter functions2 counters with Up/Down counting, partial/total functions.
- Tachometer Input FunctionsFor encoder Push/Pull or Line/Driver mono-/bidirectional up to 100KHz
- Tachometer FunctionsMaximum peak / Minimum peak
- Totalizer FunctionPulse counting from flow or flow sensors
- Display of Process and Setpoint nameSet as text value with max. 16 alphanumeric characters
- Display settingsFrom 1..4 variables per page, max 12 variables
- Unit displaySelection of measuring unit to be displayed
- Maximum number of displayed digitsDynamic variable scaling, up to 10 digits with sign (32 bits)
- Multilingual menuEnglish/Italian/German/French/Spanish
- Software parameter configurationMemory Card, software LABSOFTVIEW, codes EASY-UP - Programming via APP (NFC) "MyPixsys" for Android and iOS devices
- Software protectionCommand setpoints/alarms - Password for parameter access
- Communication protocolsModbus RTU