This stationary differential pressure transmitter detects positive and
negative differential pressures and converts the values into electrical signals.
Possible applications include cleanrooms, machines, filter technology, and heating,
ventilation and HVAC systems .
It can be used to measure differential
pressure of non-aggressive, non-combustible gases up to a pressure of 10 kPa.
The device may only be used in the approved measurement range according to type label.
ORDERING CODES |
2000.40.002 - 2000.40.209 |
---|---|
Measuring ranges |
+/- 50 Pa |
Accuracy @ 25°C |
+/- 0,3% F.S. |
Operating temperature |
0...+50°C |
Analogue output |
4..20mA |
Power supply |
2-Wire Connection - 15...32 V DC |
Display |
LC - 3 1/2 digits |
Process connection |
Standard for pipe DN 4 or 6 mm |
Material |
ABS |
Sealing |
IP67 |
Certifications |
CE - UKCA |