This temperature transmitter for DIN/B head converts a signal acquired via PT100, PT1000, Ni100 probes or thermocouple into a current signal for 4..20 mA loop (2-wire technology).
A version with galvanic isolation is also available (code 2000.35.015).
Unique features is the programming via NFC technology, not requiring the devices to be powered up. User can chose between a dedicated NFC programmer and RF-Programmer software on Pc or App MyPixsys on smartphone available on Play Store.
- DimensionsØ 45 mm, 23 mm
- MaterialNylon (PA66)
- WeightApprox. 30 g
- SealingBox and terminal blocks: IP20
- Operating conditionsTemperature -40+85 °C, humidity 30..90 uR%
- CertificationsCE, UL
ORDERING CODES |
2000.35.010 |
2000.35.015 |
---|---|---|
Power supply |
Loop Power (2 wires connection) operating range 6-32 Vdc | |
Analogue inputs |
1 x selectable among Thermoresistances PT100, PT1000, Ni100 - 2/3/4 wires |
1 x selectable among Thermocouples K, S, R, J, T, N, B, E - Thermoresistances PT100, PT1000, Ni100 - 2/3/4 wires |
Sampling/response time |
300 mS / 600 mS | |
Rejection |
50-60 Hz | |
Output resolution |
2 μA | |
Max. transmission error |
0,1% f.s o 0,2°C | |
Temperature coefficient |
< 100 ppm | |
Cable resistance |
Max 20Ω | |
Over-range output |
f.s. + 5°C | |
Under-range output |
f.s. - 5°C | |
Error output |
Selectable between 21,5mA or 3,8mA | |
Current output protection |
30 mA |
- Data Logger functionTempo di campionamento 1..3600 S - 2800 campionamenti - buffer circolare
- Control algorithmsON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportional
- TuningManual or automatic
- Alarm modeAbsolute / Threshold, Band, High / Low deviation. Alarm with optional Manual reset. Loop Break Alarm
- Double P.I.D.Heating / Cooling with double P.I.D.
- Soft-StartRising gradient expressed as Degrees / Hour or fixed output percentage
- Open / Close logicOpen / Close logic for motorized valves
- Software parameter configurationMemory Card, software LABSOFTVIEW, codes EASY-UP - Programming via APP (NFC) "MyPixsys" for Android and iOS devices
- Software protectionLock of control / alarm setpoint / Access to parameters by password
- Communication protocols
- PLC Logic programming
- Graphical interface programming
- VPN
- 2000.35.010RTD -4...20MA CONVERTER - version RTD
- 2000.35.015TC-RTD 4...20MA CONVERTER - version TC/RTD isolated
- ACCESSORIES' CODES
- 2000.35.099RFID PROGRAMMER > BLUETOOTH
- 2000.35.012RFID PROGRAMMER > USB