ATR264 is a programmer dedicated to the automation of small industrial ovens or laboratory ovens, dryers, heat treatment systems, and in general the management of a process involving cycles/profiles with control of the process variable in relation to time.
ATR264 allows the programming of 15 cycles/profiles, each one including up to 30 steps/segments, all free configurable by the user as ramp/soak/cooling.
The device integrates software functions typically required in oven/furnace management: Waiting (in the case the process is delayed in comparison to programmed setpoint) and Cycle Recovery mode (after any power failure). Special function for gas kilns management are available (code -13ABC).
Like other Pixsys programmers, ATR264 stands out for user-friendly interface and programming mode even for inexperienced operators.
Parameter configuration and cycle programming is possible via MyPixsys App on smartphone thanks to NFC/Rfid technology or on PC with MyPixsysLab software as well as directly from keyboard.
- Dimensions48 x 48 x 80mm
- MaterialBox: PC UL94V2 self-extinguishing, front panel: PC UL94V2
- WeightApprox. 185 g
- SealingFront panel: IP65, Box and terminal blocks: IP20
- Operating conditionsTemperature 0-45 °C, humidity 35..95 RH%
- CertificationsCE, UL (-12ABC-T only)
ORDERING CODES | ATR264-12ABC-T | ATR264-13ABC |
---|---|---|
Power supply | 24...230 V AC / DC ±15% 50/60 Hz - galvanic isolation 2,5KV | 24...230 V AC / DC ±15% 50/60 Hz - galvanic isolation 2,5KV |
Power consumption | 9 Watt/VA | 8 Watt/VA |
Display | Display 4 digits 0,52" white + Display 5 digits 0,3" red | Display 4 digits 0,52" white + Display 5 digits 0,3" red |
Analogue inputs | 1x Ris. 16bit, programmable for thermocouples K, J, S, R ,T, E,N, B (automatic compensation of cold junction -25...85°C, accuracy @25°C ±0,2% F.S. ±1 digit F.S.), Thermoresistances PT100, PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K), Process signals 0-20/4..20mA, 0-1/0-5/0-10V; 0..60mV, Potentiometers F.S. 1....150Kohm | 1x Ris. 16bit, programmable for thermocouples K, J, S, R ,T, E,N, B (automatic compensation of cold junction -25...85°C, accuracy @25°C ±0,2% F.S. ±1 digit F.S.), Thermoresistances PT100, PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K), Process signals 0-20/4..20mA, 0-1/0-5/0-10V; 0..60mV, Potentiometers F.S. 1....150Kohm: Current transformer 50mA |
Digital inputs | 2 PNP | 2 PNP |
Digital outputs | 2 x PNP 12VDC - 25mA o 24VDC - 15mA selectable by parameter | 2 x PNP 12VDC - 25mA o 24VDC - 15mA selectable by parameter |
Relay outputs | 2 x (2 A - 250 V AC resistive load) | 3 x (2 A - 250 V AC resistive load) |
Analogue outputs | 1 x 4..20 mA (40000 points ± 0,2% F.S ) o 0..10 V DC (40000 points ± 0,2% F.S.) | 1 x 4..20 mA (40000 points ± 0,2% F.S ) o 0..10 V DC (40000 points ± 0,2% F.S.) |
Serial communication | RS485 (1200..115200 Baud) galvanically isolated |
- Cycles / Profilesup to 15
- Steps/Segmentsup to 30 for each cycle ( max duration per step 99.59 hh.mm)
- Control algorithmsON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportional
- TuningManual or automatic
- Alarm modeAbsolute / Threshold, Band, High / Low deviation. Alarm with optional Manual reset. Loop Break Alarm
- Dual P.I.D.Heating / Cooling with dual P.I.D.
- Open / Close logicsOpen / Close logics for motorized valves command
- Software parameter configurationSoftware MyPixsysLab, App MyPixsys
- Data protectionLock of cycles - Access to parameters by Password