Indicator / panel meter STR551 is designed for process acquisition and retransmission via analogue output.
The monochrome OLED graphical display supports process trend displays with programmable sampling time and bar-graph representation with thresholds typically used for level, flow and dosage measurements.
Analogue input is configurable by parameter for a wide range of temperature sensors and process signals in mA and volts. Linearization is customizable up to a maximum of 16 points, useful on irregularly profiled tanks.
Process-related mathematical functions such as Totalizer and Sum are also implemented.
Connectivity is provided by standard RS485 with Modbus RTU/Slave protocol.
For maximum flexibility of use, there is also a choice of horizontal or vertical installation.
User can program the device using the intuitive interface with multi-language text menus of the MyPixsys App thanks to integrated NFC communication.
- Dimensions96x48 (Front panel) x 48 mm (1/8Din)
- MaterialBox: polycarbonate V0. Front cover: silicone rubber
- WeightApprox. 165 g
- SealingFront panel: IP54, Box and terminal blocks: IP20
- Operating conditionsTemperature 0..45 °C, humidity 35..95 RH%, max altitude 2000m
- CertificationsCE, UL
ORDERING CODES | STR551-12ABC-T128R |
---|---|
Power supply | 24..230 V AC / DC ±15% 50/60 Hz - galvanic isolation 2,5KV |
Power consumption | 8 Watt/Va |
Display | 2.42" monochrome (yellow) OLED graphic display, 128 x 64 |
Analogue inputs | 1 x Ris. 16bit, programmable for thermocouples K, S, R, J, T, E, N, B (automatic compensation of the cold junction -25..85°C, Toll. @25°±0,2% F.S. ±1 digit F.S.), Thermoresistances PT100, PT500, PT1000, Ni100, Ni120, PTC 1K, NTC 10K (β |
Sampling time | Programmable up to 4,1 mS (frequency up to 242 Hz) |
Digital input | 2x PNP |
Analogue outputs | 1x 0..10V (60000 points) 1x 0/4..20mA (60000 points) |
Digital Outputs | - |
Auxiliary Output | 12/24 VDC - 25mA max for sensor power supply |
Relais Outputs | 2x 2 A - 250 V AC resistive load |
Serial communication | RS485 (1200..115200 Baud) galvanically isolated |
USB | 1x micro USB for programming via PC with LabSoftView |
- Alarms regulationON - OFF with hysteresis
- Alarm modeAbsolute / Threshold, Band with instantaneous/delayed/retentive/by digital input activation, Sensor failure / Activation by serial line
- Sum FunctionSum different process measurements over time By digital input or by keyboard
- Totalizer FunctionVisualisation of instant process value and total value since last reset
- Latch-on functionSemi-automatic setting of limits/ calibration values for analogue inputs
- Graphic functionTrend display with time base settable from 1sec to 3600sec total 4K memory words
- Measure unit visualizationSelection of different measuring units
- Multilingual menuEnglish/Italian/German/French/Spanish
- Analogue retransmissionRetransmission of process values / setpoints to analogue outputs
- Software parameter configurationMemory Card, software LABSOFTVIEW, codici EASY-UP - Programming via APP (NFC) "MyPixsys" for Android and iOS devices
- Software protectionsCommand setpoints / alarms - Password for parameter access
- Communication protocolsModbus RTU